Performance Data remote control.

Solution:
Overall
Based on the Performance table:
1. Refer to the Indoor DB column,
25°C is located between 24°C and 27°C for 16oCWB (Thus, Interpolation need to be applied)
25°C is located between 24°C and 27°C for 19oCWB (Thus, Interpolation need to be applied)
2. Refer to the Indoor WB column,
17°C is located between 16°CWB and 19°CWB for 25oCDB (Thus, Interpolation need to be applied)
3. Refer to the Outdoor DB column,
37°C is located between 35°C and 40°C. (Thus, Interpolation need to be applied)
Please follow the steps below in order to get the required capacity.

Air discharge direction can be adjusted in four directions, manually or automatically by using LCD remote control.